AC200 load bank

200 kW AC 3-phase | 67kW AC 1-phase

Product information

 

Operating and maintenance manual PDF

Technical data sheet PDF

General arrangement drawing PDF

Technical specification

 

Voltage ratings options

 

The AC200 is available 3 versions for the following voltage ratings:

400V

415V

480V

All versions are suitable for frequencies of 50Hz or 60Hz. Other voltages and frequencies are available on request.


Power ratings (all versions)

 

3-phase

Load step resolution 5.0kW

Max. capacity 200kW

 

1-phase

Load step resolution 1.67kW

Max. capacity 66.7kW


Control and Ventilation

 

Manual controls

System on/off pushbuttons

Supply rotary selector switch

Emergency stop

Control interface 7” touch screen display

Cooling Forced convection

Fans 1 x 3.7kW AC fan, axial type

Noise 88dB at 1m

Control supply 3-phase AC, voltage to suit version

Source Internal (supply under test) or external supply (recommended)


Connection Interfaces

 

Load connections

4 x Powersafe sockets (3P+N)

1 x PE M16 Stud connection

External control supply 1 x EN 60309 3P+PE 16A

Data downloads 2 x USB Type A

Networking/ remote 2 x RJ45


Operating Environment

 

Suitable for indoor use only

Ambient temperature -10°C to 50°C

Humidity 95% RH

Ingress protection

IP23 Load enclosure

IP54 Control cabinet 


Construction

 

Resistor elements Stamped grid and wire coils

Element material High grade stainless steel

Main enclosure

Dual layer; galvanised sheet steel, painted RAL9002 grey 

Portability

4 x heavy duty castors (2 x braked)

fork lift pockets

optional lifting frame includes 4 x lifting eyelets


Weight and Dimensions

 

Load bank only

Length 1080mm

Width 800mm

Height 1353mm

Weight 240kg

 

with lifting frame

Length 1276mm

Width 896mm

Height 1503mm

Weight 285kg


Safety

 

Electrical protection

Over current and short circuit fuse protection
 
Over voltage protection (via control system)

Thermal protection

PT100 monitoring (load and control compartments)

PT100 healthy status

Airflow status

 Optional extras

Remote Control - the Digi-load Remote provides the ability to control a load bank via a wired connection. It can also be used as the single point of control for a network of load banks. Housed in a rugged IP66 case it includes a 10” touch screen, emergency stop and 2 x USB  data ports.

Network capability - when this hardware capability is enabled the load bank can be connected with other load banks via Modbus TCP to create a centrally controlled network.

Protective PVC cover - available for additional protection during transport or storage.

Supply cables - made to order to the desired length and with supply side connection method to suit the intended use.

Anchor bolt mounting plates - available for permanent installation. (no-cost option since supplied instead of heavy duty castors)