AC6 load bank

Product support page

Product information

 

Operating and maintenance manual .PDF

General arrangement drawing .PDF .DWG

Product data sheet .PDF

Technical specification

 

Voltage rating options

 

The AC6 is available in 2  standard versions with the following voltage ratings

Dual; 110V and 230V
Single; 230V only 

Both versions are suitable for frequencies of 50Hz or 60Hz.  Other voltages and frequencies are available on request.

 

Power Ratings

 

110V AC 1-phase

Maximum capacity 3.3kW

Load step resolution 0.30kW

 

230V AC 1-phase

Maximum capacity 6.0kW

Load step resolution 0.33kW


Control and Ventilation

 

Manual controls

6 x Load section toggle switches

Single; 1 x on/off MCB switch

Dual; 1 x 110/off/230 rotary selector switch

Control interface

Manual control (described above)

1 x Analogue volt meter

1 x Analogue frequency meter

1 x Analogue current meter

Cooling Forced convection, horizontal orientation

Fans 1 x AC axial type

Control supply 230V AC 1-phase 50/60Hz

Source Internal, taken from supply under test


Connection Interfaces

 

Load connections

Single; 1 x 1.5m integrated lead with 230V 32A IEC60309 inline socket (1P+N+PE)

Dual; as single plus 1 x 1.5m integrated lead with 110V 32A IEC 60309 inline socket (1P+N+PE)


Operating Environment

 

Suitable for Indoor use only

Ambient temperature -10°C to 50°C

Humidity 95% RH

Ingress protection IP20


Construction

 

Resistor elements Wound steel tape

Element material High grade stainless steel

Enclosure Aluminum, painted RAL9002 grey

Portability 1 x protective lid with integrated carry handle


Weight and Dimensions

 

Length 495mm

Width 220mm

Height 550mm

Weight 12kg


Safety

 

Electrical protection Short circuit protection via MCB(s)

Optional extras

Supply cables made to order to the desired length and with supply side connection method to suit the intended use.

PVC storage cover available for protection during transport or storage.