AC500 load bank

Product support page

Downloads

 

Technical data sheet PDF

Operating Manual PDF

General arrangement drawing PDF

Technical specification

 

Voltage ratings options

 
 

The AC500 is available 3 versions for the following voltage ratings:

400V

415V

480V

All versions are suitable for frequencies of 50Hz or 60Hz. Other voltages and frequencies are available on request.

Power ratings

 

3-phase

Maximum capacity 500 kW

Load step resolution 25.0 kW

 

1-phase

Maximum capacity 166.7 kW

Load step resolution 8.33 kW


Control and Ventilation

 

Manual controls

System on/off pushbuttons

supply rotary selector switch

emergency stop

Control interface 7” touchscreen

Cooling Forced convection

Fan 1 x 7.5kW AC fan, axial type

Control supply 3-phase AC, voltage to suit version

Source Internal (supply under test) or external supply


Connection Interfaces

 

Load connections

10 x Powerlock drainsockets (2x 3P + N + PE)

External control supply 1 x EN 60309 3P+PE 32A

Data downloads 1 x USB Type A

Networking and remote 1 x RJ45


Operating Environment

 

Suitable for outdoor use

Ambient temperature -10°C to 50°C

Humidity 95% RH

Ingress protection

IP23 Load enclosure

IP54 Control cabinet  


Construction

 

Resistor elements Stamped grid and wire coils

Element material High grade stainless steel

Base platform Hot-dip galvanised steel 

Main enclosure

Dual layer; galvanized sheet steel, painted RAL9002 grey 

Hot-dip galvanised steel

Portability

4 x heavy duty castors (2 x braked)

fork lift pockets

optional lifting frame includes 4 x lifting eyelets


Weight and Dimensions

available in two options

 

Load bank only

Length 1380mm
Width 800mm
Height 1353mm
Weight 310kg

 

With lifting frame

Length 1476mm
Width 896mm
Height 1503mm
Weight 370kg


Safety

 

Electrical protection

Over current and short circuit fuse protection 

Over voltage protection (via control system)

Thermal protection

PT100 monitoring (load and control compartments)

PT100 healthy status

Airflow status

Optional extras

Remote Control – the Digi-load Remote provides the ability to control a load bank via a wired connection. It can also be used as the single point of control for a network of load banks. Housed in a rugged IP66 case it includes a 10” touch screen, emergency stop and 2 x USB  data ports.

Network capability – when this hardware capability is enabled the load bank can be connected with other load banks via Modbus TCP to create a centrally controlled network.

Protective PVC cover available for additional protection during transport or storage.

Supply cables made to order to the desired length and with supply side connection method to suit the intended use.

Anchor bolt mounting plates available for permanent installation. (no-cost option since supplied instead of heavy duty castors)