Technical specification
Ratings
Suitable for frequencies of 50Hz or 60Hz. Other voltages and frequecies available on request.
3-phase
Voltage 400V AC
Maximum load step resolution 1.25kW
Max. capacity 98.75kW
1-phase
Voltage 230V AC
Maximum load step resolution 0.42kW
Max. capacity 32.9kW
Control and Ventilation
Manual controls
16 x On/Off push buttons for load sections and control (fan)
1 x Phase selector rotary switch for voltage measurement
1 x Phase selector rotary switch for current measurement
Emergency stop
Control interface
Manual Control (described above)
7 x load section lamps
1 x control fan healthy lamp
1 x external supply source lamp
1 x Analogue Volt meter
1 x Analogue frequency meter
1 x Analogue current meter
Cooling Forced convection, vertical orientation
Fans 1X AC axial type
Noise 90dB at 1m
Control supply 230Vac 1-phase 50Hz
Source Internal (supply under test) or external supply (automatic, when connected)
Connection Interfaces
Load connections
4 x Powersafe sockets (3P+N)
1 x PE M12 Stud connection
Measurement points
2 x external meter points for voltage
2 x external meter connection points for current
External control supply 1 x C14 socket (L+N+PE)
Operating Environment
Suitable for indoor use only
Ambient temperature -10°C to 50°C
Humidity 95% RH
Ingress protection IP20
Construction
Resistor elements Wire coils (sheathed)
Element material Stainless steel
Main enclosure Aluminium, painted grey (RAL9002)
Internal base frame Stainless steel, un-painted 2B finish
Portability 1 x Push handle and 4 x Heavy duty castors
Weight and Dimensions
Length 1040mm
Width 670mm
Height 940mm
Weight 123kg
Safety
Electrical protection Over current and short circuit fuse protection
Thermal protection Thermostat cut-out
Optional extras
Supply cables made to order to the desired length and with supply side connection method to suit the intended use
Protective PVC cover available for additional protection during transport or storage.
Anchor bolt mounting plates available for fixed location installation.
Measurement leads with plugs for voltage and current feed to external meter.