DC7000 load bank

3100kW | 0 to 7000A and up to 2000V DC

Key features

 
dc7000.jpg
 
 

For performance testing of diesel electric locomotives up to 4000hp rating, with easy-to-use resistance adjustments.

 

DC capacity

3100kW, 0 - 7000A continuously at up to 2000V DC. The load consists of twin 14-section fan-cooled resistor ducts with fans, starters and controls. The optional two main load isolating contactors and an integrated off-load switch panel permitting the pre-selection of any one of more than 200 values of resistance between 0.026Ω and 3.3Ω.

Connection scheme

The off-load knife switches allow for the reconnection of the twelve resistors in each stack into more than 200 different configurations with a range from .026Ω/7000A through to 3.3Ω/600A. There are intermediate points to suit the majority of loco alternators up to 300hp rating.

 
 

Construction

The fans, resistors and switchgear are all built in to a single sheet steel frame with hinged lockable access doors, air intake screens and (optionally) hand-operated outlet louvres. Paint finish is RAL9002 grey powder coat the enclosure is designed for floor mounting with bottom cable entry. Fan motor and control voltages are set to suit customer’s own available supply voltage and frequency.

Resistor element

Flat strip elements, type EN Each bank is contained in a fully insulated duct section with two independent levels of 3kV electrical insulation. The resistor elements are manufactured from a 60:23 nickel-chrome stainless steel. This is a high-grade stainless steel with excellent corrosion resistance properties and a low (0.12%/°C) temperature coefficient of resistance, giving very stable resistance values over the whole range of operation.

 

Technical specification

Ratings

Maximum voltage 2000 V DC

Maximum current 7000 A

Maximum capacity 3126kW

 

Control and Ventilation

Manual controls

14 x Off-load knife switches

on/off push button control for fans

1 x local emergency stop

Instrumentation

1 x 4000A/1mV shunt

1 x Digital power meter with 4-20mA output

Cooling Forced convection, vertical orientation, horizontal outlet

Fans 2 x 27kW AC fan, axial type

Control supply 3-phase AC, voltage and frequency to suit order

Source External supply


Load controls Main load connections to suit order, 2 x M12 PE bonding

External control supply To suit order

Connection Interfaces


Suitable for Indoor use only

Ambient temperature 5°C to 40°C

Ingress protection

IP23 load enclosure

IP54 Control cabinet 

Operating Environment


Construction

Resistor elements Steel strip

Element material 60-23 NiCr high grade stainless steel

Main enclosure Sheet steel, painted RAL9002 grey

Exhaust air duct Stainless steel grade 304L, un-painted 2B finish


Weight and Dimensions

 

Length 2750mm

Width 1900mm

Height 2650mm

Weight 2700kg


Access protection Lockable cabinet doors, interlocked with trapped key isolator safety logic

Thermal protection Airflow status alarm via pressure switch

Safety

 Optional extras


Main Contactors – The two main contactors carry the maximum continuous thermal current of 7000A and have a peak breaking capacity of 1000A, allowing for on-load isolation from the locomotive generator after the excitation has been reduced. For safety, the contacts are mechanically latched and have a separate trip coil so that there is no possibility of accidental opening during testing.

Weather proof louvres – For periods of long term storage it is recommended to protect the load bank from water and particulate ingress. Optional extra is to have hand-operated weather proof louvres integrated into the outlet ducts can provide this protection.

 

Documentation downloads

Technical data sheet PDF